45°C inlets just killed the chiller. Most people haven't noticed yet

https://www.theregister.com/hpc/2026/11/26/45c-inlets-just-killed-the-chiller-most-people-havent-noticed-yet/5311831

Comments

viktorcodeNov 26, 2026, 7:09 PM
> We're approaching a point where industry advances are answering many of the objections (the real ones, not the hysterical ones) raised by the anti-data center movement.

AFAIK the main objections are against sharing the electricity bill and tax exemptions in exchange for a paltry amount of jobs created. Does the author classify those as hysterical?

Also, the existence of technologies does not mean the data center next door will use them. For instance, many can run on closed water loops, but prefer not to, because it is cheaper.

fancyfredbotNov 26, 2026, 7:31 PM
This technology is very likely to see widespread adoption because it's much cheaper not to have chillers.

It should genuinely reduce power required for a given amount of compute which is a good thing. Probably still too much power though.

The real solution to the tax exemption issues, as well as to electrical bills, is at the ballot box and not at an Nvidia design meeting.

bigiainNov 27, 2026, 12:33 AM
I wonder how the existing install base of data centre GPUs like H100s and H200s which need water chilling will affect adoption?

And I wonder how the supply chain and existing inventory looks for near term data centre builds? I've seen speculation that there are warehouses/datacenters full of GPUs not yet in use awaiting data centre or power/water infrastructure to be completed.

guardiandemonNov 27, 2026, 2:33 PM
There are already people here on HN arguing against democracy. Just accept tech bros as your new feudal lords.
theptipNov 26, 2026, 7:55 PM
All this is easily fixable by a government that actually cares. So many commentators (and the markets) freaking out about how DC buildout is going to halt, but when you look at the demands they are easily satisfiable.

If tax exemptions are off the table, DC operators will just bid higher, including paying a lot more in up-front power commitments, or even just paying off the local communities.

The profit margins on compute are ludicrously high for the big guys, they can and will pay a lot more into the local community if that’s what’s needed to get approval in ‘27. Like, Anthropic could pay double per MW and still have plenty of margin on their inference operations.

It’s been a free for all up until now because of the federal government’s “build at all costs” stance, now the blowback has hit, and next the price will be established and the new equilibrium found.

fakedangNov 26, 2026, 9:00 PM
> The profit margins on compute are ludicrously high for the big guys, they can and will pay a lot more into the local community if that’s what’s needed to get approval in ‘27. Like, Anthropic could pay double per MW and still have plenty of margin on their inference operations.

And yet most of them decide to use aging technology just because it's cheaper and faster to deploy - like Google just chopping down prime forest land in Finland or xAI using fossil-fuel based sources for energy. They could if they wanted to but they won't because money.

distancesNov 26, 2026, 11:21 PM
> Google just chopping down prime forest land in Finland

This wasn't the problem in Finland, or at least putting it this way is misleading. It's was about 0.04% of annual tree felling in Finland. And the trees were obviously used for something, even though they were low-value boreal commercial pines.

The issue was, like you then mentioned in your other comment, that the regulations weren't followed. I think mostly everyone agrees that the outcome would've been the same, but the correct procedure must of course be followed.

theptipNov 26, 2026, 9:17 PM
Again, solve for the equilibrium.

They will do the cheapest thing that is allowed.

When those cheap things are forbidden they will do the next cheapest thing.

We could easily regulate behind the meter gas turbines (noise and/or pollution) if the feds/states wanted to.

fakedangNov 26, 2026, 10:31 PM
I specifically pointed out Finland because Google technically broke multiple laws when doing that, which is why they're now being investigated. But clearly punishment itself wasn't deterrent enough.
dan_grecNov 27, 2026, 6:28 AM
Just like for regular citizens, the punishment needs to be severe enough of a deterrent.

I remember a friend from NYC visiting Melbourne and laughing how cheap the parking violations were. “Park on the sidewalk!” He yelled. The fine was like 2 hours of paid parking in his NYC garage.

Google willfully broke the law to cut down a forest. It was not an accident. They don’t care about rules. Finland needs to show them what happens. Minimum $100 million fine plus garnered revenue for 10 years. They’ll still make billions.

db48xNov 27, 2026, 6:42 AM
That’s stupid. Those trees weren’t worth $100 million to anyone, not even the country of Finland. They didn’t cut down a whole forest, just a plot of commercial pines that were planted specifically to be harvested and made into paper or 2×4s or whatever. You should not feel outraged that they cut these trees down; they were going to be cut down anyway.
dan_grecNov 27, 2026, 8:54 AM
It’s not about the trees.

It’s about their blatant disregard for laws. They simply do whatever they want because the consequences are a joke to them (just like the guy parking on the sidewalk)

We need to make it clear that is not acceptable.

db48xNov 27, 2026, 6:08 PM
It is definitely about the trees. If they had built on an empty field then it never would have made the news, you never would have heard about it, and thus you would have nothing to be angry about.
dan_grecNov 27, 2026, 8:03 PM
If they built on an empty field without the required permits we would be talking about it.

It’s the disregard for the law that matters.

imoverclockedNov 26, 2026, 7:40 PM
This. It goes deeper though. Yes, data centers use a lot of resources but they also enable abuses of power… political as well as energy.

The rush to put data centers up has created situations where construction of entire nuclear plants are in the plans (~10 year horizon) while the short term goal of energy production is diesel based. Anyone want to wager on the odds that the nuclear plants actually get built? The planned energy production is sometimes in the small percentages of a host countries entire carbon budget.

As for political abuses, flock cameras are definitely enabled by large data centers and have been in the middle of a lot of surveillance scandals. Large layoffs by AI as well as AI slop in practically every sector of our society make it even less palatable to spend more on data centers.

It’s not uncommon for me to go shopping and the person at the checkout is bemoaning the computer in front of them. When is the last time you heard someone outside of tech get excited about a new computer? Unless it’s for games or they had none to start with, I find it to be less and less common. Data centers are just an extension of the general malaise we have created as an industry.

cucumber3732842Nov 26, 2026, 9:24 PM
>AFAIK the main objections are against sharing the electricity bill and tax exemptions in exchange for a paltry amount of jobs created. Does the author classify those as hysterical?

Voters need to look in the mirror on this one. Yeah there's a few layers of indirection but the grid is f-d up and full of perverse incentives because people demand the second coming of christ before you can run a goddamn wire.

aaron695Nov 26, 2026, 10:29 PM
[dead]
helsinkiandrewNov 26, 2026, 3:25 PM
Discussion on Nvidia blog post (429 comments) https://news.ycombinator.com/item?id=48660178

I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan

IndrekRNov 26, 2026, 3:37 PM
Rule of thumb is that 10 degrees difference makes reactions go, and things fail, twice as fast. This is not exact science, but ballpark is about right.
leoedinNov 26, 2026, 4:30 PM
Is a chip cooled with water at 45C necessarily going to be hotter than a chip cooled by air? I imagine the temperature differentials between chip and coolant on a water cooled setup are much better than the differential between chip and airflow on a typical air cooled setup.
arghwhatNov 26, 2026, 4:39 PM
We strictly speaking never do pure air-cooling in this context.

Traditional water-cooling transfers heat to a fluid, which is then moved to a large radiator to be cooled by air.

Traditional "air-cooling" transfers heat to a phase-changing fluid (heat-pipe), which is then moved to a large radiator to be cooled by air.

Only differences are the type of and amount of fluid, as well as the presence of pumps. Phase-change beat using a fluid as a thermal buffer by quite a bit. The benefit of water is that it's easy to provide massive thermal inertia, and the ability to transfer the heat to a far larger external radiator than could be implemented internally with heat-pipes.

landgenootNov 26, 2026, 3:58 PM
What kind of reactions? What is a typical component that fails do to heat?
magicalhippoNov 26, 2026, 4:38 PM
It stems from the Arrhenius equation[1] for chemical reactions.

Such a relationship also seems to hold for semiconductors, increase the componentoperatingtemperaturewith 10C and you roughly half the component lifetime[2]. However thermal cycling and similar adds additional stress so it's not as simple a relationship as with chemicals.

[1]: https://en.wikipedia.org/wiki/Arrhenius_equation

[2]: https://www.ti.com/lit/an/snva509a/snva509a.pdf

lazideNov 26, 2026, 4:23 PM
(Almost) everything chemical, which is at some level almost everything.

Electrical resistance also (generally) increases with temperature, which causes non-linear effects.

(More resistance == more heat, which makes more resistance until the magic smoke comes out, which typically causes a short and resistance drops to zero)

There are some very weird exceptions, but if you don’t know what they are, it won’t help you.

labcomputerNov 26, 2026, 4:49 PM

  > Electrical resistance also (generally) increases with temperature, which causes non-linear effects.
For conductors and insulators, yes. But for semiconductors, resistance drops with temperature because more charge carriers are promoted to the conduction band.
lazideNov 26, 2026, 5:10 PM
More leakage current though, which causes increased noise, which usually causes increased power use to compensate - or errors. Or just more ‘waste’ power use directly.

See my comment about how it generally doesn’t actually help you.

Cryocooling semiconductors is a thing for a reason.

adrian_bNov 27, 2026, 11:39 AM
The resistance drops with temperature only for semiconductors with low concentrations of doping impurities.

Almost all the parts of the semiconductor devices used in practice have doping levels high enough so that their resistance grows with temperature.

In such doped semiconductors, there exists a temperature threshold above which the resistance begins to decrease with temperature.

That threshold temperature is chosen to be much above the normal operating temperature of the device. If that temperature threshold is reached, the so-called thermal breakdown of the device can occur, when due to positive feedback, the electric current through the device increases until the semiconductor crystal is melted and destroyed.

lukaNov 26, 2026, 4:39 PM
In semiconductors, resistance decreases with an increase in temperature.
adrian_bNov 27, 2026, 11:45 AM
See my comment above.

With the exception of NTC thermistors, almost all the semiconductor devices used in practice are made with doped semiconductors, whose resistance increases with temperature, until a threshold that is much greater than the acceptable operating temperature range, so it is never reached during normal operation (but only when the device may be destroyed by overheating).

octoberfranklinNov 26, 2026, 4:05 PM
Electromigration in the wiring on a silicon chip.
andaiNov 26, 2026, 3:46 PM
So... good for Nvidia's profits?
dcrazyNov 26, 2026, 4:30 PM
If the MTBF is still longer than the upgrade cycle, it won’t impact profits.
m463Nov 26, 2026, 6:18 PM
wow, that makes me think of used cars that last just a bit longer than lease turnover.

(also, 45°C < current global warming number. if we get another 2°C will it become 47°C?)

notatoadNov 26, 2026, 6:01 PM
that's an interesting question... what as the current relationship between the MTBF and the upgrade cycle, and if they're not aligned then what happens to all that old gear?

are datacenters just chucking all their H100 chips in the bin because they're old now?

andaiNov 27, 2026, 3:43 PM
I wanted to say there must be a market for them (esp. AI startups) but then I realized the scale might be to small for it to make sense, if it would be a bunch of small orders.

https://xkcd.com/1737/

esternaNov 26, 2026, 8:31 PM
I would suppose it matters very little as long as 95% of components become obsolete before they fail.
bob1029Nov 26, 2026, 4:33 PM
Semiconductors are unique in that higher temperatures are sometimes preferable for certain electrical characteristics.

I would worry more about thermal cycling and temperature gradients across the die. A machine that runs at 100% 24/7/365 tends to be pretty reliable.

hdndjsbbsNov 26, 2026, 4:49 PM
There is a well-known formula, Black's Equation, which computes mean time to failure for chips caused by electromigration. Temperature is absolutely a factor. In industry it is very common to accelerate MTBF testing by increasing ambient temperature in a heating chamber, because you can predictably calculate MTBF at standard operating temps based on testing at elevated temps.

Electromigration is an unavoidable problem that increases at lower process sizes and higher temperatures. Cutting edge chips at high temps will fail faster without sufficient redundancy designed in.

bob1029Nov 26, 2026, 4:54 PM
Black's equation is like a spherical cow approximation when you are looking at something that uses HBM and complex assembly techniques.
hdndjsbbsNov 26, 2026, 6:46 PM
You're not gonna complexly assemble your way out of electrons and atoms colliding. Like I said you can trade off surface area to build in redundancy but for a given node size and temperature electro migration is an unavoidable fact.
unrented7977Nov 26, 2026, 6:53 PM
Your HBM and complex assembly is, in reality, a bunch of spherical cows glued together. Each individual component has its own MTBF, and when any one of them dies, the whole assembly goes with it.

Complex assembly increases failures, it does not decrease them.

tomaskafkaNov 26, 2026, 8:01 PM
Why would a billion dollar company dependent on how much new GPUs you buy lie about the component lifespan impact?
iamnielsNov 26, 2026, 3:33 PM
This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.

I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.

InsidiousWombatNov 26, 2026, 4:29 PM
power/fiber locations matters far more, that's why we aren't seeing all of the datacenters go to alaska
citrin_ruNov 26, 2026, 9:22 PM
Fiber is cheap compare to the current CAPEX spending and can be brought to any reasonable location. Power does matter but as long as AI companies can burn fossil fuels and don't pay for externalities what matter for them is not the price (which is low for them) but availability of power now (the main bottleneck).
apiNov 26, 2026, 3:36 PM
Also reduces energy use and nukes the water objection.
MrBuddyCasinoNov 26, 2026, 4:42 PM
Which is bs anyway.
dgellowNov 26, 2026, 6:02 PM
It’s not bullshit, the issues are localized but do exist. Not all water sources are equivalent, not all locations have the same water resources, and there is an impact on local communities.
MisterMunchkinNov 26, 2026, 7:37 PM
Data centres don’t use water anywhere except America. It’s like shitting in your pants and then asking why pants always have shit in them. You don’t have to do it.
tadfisherNov 26, 2026, 8:38 PM
Two points:

- In other parts of the world, public resistance is backed by collective action. American protests are tame and non-violent, so it's cheaper to ignore them until the next election.

- The tradeoff for closed-loop cooling is power use, e.g. chillers. The physics require that additional energy conversion to produce heat which must be rejected upstream of the DC. The most power-efficient form of rejecting heat is to dump it into water and then into the air via cooling towers. I am willing to bet that a non-zero percentage of generating plants in, say, Europe are cooled via this method, because it is the cheapest way to do it!

kodebachNov 27, 2026, 12:39 AM
The most energy efficient system is actually to skip the "then into the air" part and hook the DC up to a district heating system. That way you can actually use the waste heat. (ICYDK district heating can also be used for hot water supply, so it's not just for cold places and winter months)

If that's not an option the next best thing would be using river water of a river large enough that the waste heat doesn't negatively impact the ecosystem.

But the US is building DCs where land is cheap i.e. deserts, which is why they can't use those efficient cooling methods.

tadfisherNov 27, 2026, 5:53 PM
It's funny, the wastewater discharge option didn't cross my mind because my state (Oregon) has rather strict regulations and isn't common for data centers here. I believe one of Amazon's campuses here distributes the wastewater for irrigation, but that has exacerbated nitrate concentrations.
swed420Nov 26, 2026, 4:50 PM
The water argument always seemed like bs engineered by pro-DC people:

1) Disseminate fake or exaggerated concerns about water

2) Uninformed people include them in their anti-DC arguments

3) Point out the antis are wrong about water, and imply their other concerns should be ignored entirely

aka "motte-and-bailey fallacy" iirc

BurningFrogNov 26, 2026, 8:05 PM
I really don't think the world work like this.

Has any operation like this ever succeeded, or even been tried?

rixedNov 27, 2026, 4:31 AM
Nietsche already wrote about this way of fighting an argument somewhere. I believe it's been one of the primary tool in any professional propagandist toolbox since this discipline have been established as a science in the late 19th.
K0baltNov 26, 2026, 10:51 PM
It is absolutely part of the stock -and -trade of grey area PR companies. Making up a debunkable objection arguing adversarial views was suggested to me many times as a way to increase visibility. It’s one of the most innocuous of the questionable services that end up on the price list.
fastballNov 26, 2026, 5:25 PM
I think this would be called "false-flagging" (instead of motte-and-bailey) if it was actually a secret pro-data-center astroturfing campaign (which I doubt).
swed420Nov 26, 2026, 7:20 PM
False flag might pertain to mass deployment of the technique, but the fallacy itself doesn't have limits on deployment scale afaik.

> which I doubt

Regardless of name, it's a time-tested widely deployed technique by the Uniparty to prop up the illusion of democracy while serving capital interests. It'd be weird if they used it for everything except DCs, though I suppose theoretically possible.

https://en.wikipedia.org/wiki/Uniparty

"Sure, you can have your social media to debate the topics of the day, but we're going to seed it with catnip and false dichotomies." - Elites

red75primeNov 26, 2026, 5:29 PM
The other concerns are "Ahhh! DCs use energy! And they are noisy."
swed420Nov 26, 2026, 5:43 PM
I've seen subcomponents to the energy concern:

- Grid upgrade costs provoked by building DCs raises utility costs for small-time consumers

- Adding heat to an already overheating planet

Noise seems like a valid complaint if the area is used to peace and quiet.

There's also a lingering anxiety about mass unemployment, since at this stage almost everybody knows someone who's been laid off and struggles to find work among an increasing pool of unemployed people. Talk of massive DC expansions from AI while the job loss topic is ignored makes for poor optics.

red75primeNov 27, 2026, 5:45 AM
> Adding heat to an already overheating planet

Climate reports include "we also need to sequester a few hundred billion tonnes of CO2 after we've gone carbon neutral" in a small print (to not discourage going carbon neutral). Good luck doing that without the help of AI with aging and dwindling population of 2050s without staining the economy to a breaking point.

The energy production is a drop in a bucket of solar energy trapped by greenhouse gases.

dgellowNov 26, 2026, 6:02 PM
Which are perfectly valid concerns for local residents
red75primeNov 27, 2026, 5:40 AM
Those aren't specific to DCs, but apply to any production facilities. So, it's not environmental impact itself. but a perceived usefulness/impact score that drives the judgement.
red75primeNov 27, 2026, 7:52 AM
ETA: and while environmental impact can be quantified, the perceived usefulness is heavily influenced by people's opinions on AI.
MrBuddyCasinoNov 26, 2026, 5:01 PM
No it was simply an op along political lines, same as the Huang ouster btw.
jayd16Nov 26, 2026, 7:00 PM
You're going to have to explain this considering his ousting and return were under the same administration, same board...
swed420Nov 26, 2026, 5:05 PM
It being an op along political lines need not be mutually exclusive. What I described would be part of that op.
ExoticPearTreeNov 26, 2026, 3:33 PM
ASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).

The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.

Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.

As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.

quickthrowmanNov 26, 2026, 3:31 PM
Well, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.

1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling

Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.

https://mitchellt.com/2018/10/23/why-is-55-so-important.html

The same set of companies that make chillers are the ones that make dry coolers: Carrier, Daikin, Trane, York (JCI), Liebert (Vertiv)

__MatrixMan__Nov 26, 2026, 3:18 PM
That's conveniently hot enough for a hot shower. It would be cool to see more district heating/cooling efforts.
andaiNov 26, 2026, 3:47 PM
In Eastern Europe there's a lot of places that get hot water thru underground pipes from a power plant.

Obviously has downsides though, one time they were renovating and we didn't have hot water for a few weeks.

lucaspillerNov 26, 2026, 4:10 PM
My city has district heating which covers around 500k people. The peak output of all the heat plants combined is 239 MW, which is around the same heat output as one or two large data centres.

There are no power plants in my city, so to generate the heat there are heat plants which burn natural gas, biomass or (if supplies get low) something similar to bunker fuel.

Of course it's seasonal, but I'm sure the cost of getting rid of the excess heat in summer would outweigh the current costs of the system (it's more expensive per kWh than a gas boiler), as well as the environmental benefits from not burning all this stuff near where people live.

TeMPOraLNov 26, 2026, 4:22 PM
Demand for hot water would be more consistent throughout the year if not for changes to washing machines and detergents that make it possible to do laundry with absurdly cold water (20 degrees) - which I believe is what makes "fast fashion" possible (the stuff would likely melt apart after few rounds in 60 degrees).
gambitingNov 26, 2026, 4:48 PM
I'm not sure I follow - washing machines heat their own water and only take in cold, how does that change the demand for hot water from the network?
amoshebbNov 26, 2026, 5:04 PM
In America washing machines have two hoses, one for hot (and typically no internal heater at all) and dish washers typically take in hot water too.
wafflemakerNov 26, 2026, 5:13 PM
Which is why you can improve efficiency of your American dishwasher by running hot water for a minute (until it gets hot) before you start it.
toomuchtodoNov 26, 2026, 5:58 PM
Point of use heaters at the inlet are also an option if you’re already installing one at the sink. Think 120V 15-20A resistance heat to heat the water when use starts until hot water from the hot water heater arrives. Is it better or worse than a recirculating pump? Depends, have to model each way.
ScoundrellerNov 26, 2026, 7:06 PM
I’ve lived in a building where the recirc prematurely caused leaks on the pex hot water return lines on every riser.

Fun times!

toomuchtodoNov 26, 2026, 7:28 PM
There are people who swear by pex, and as a hobbyist enthusiast in the building science domain, I remain wildly allergic to it versus copper (regardless of the cost and labor premium).

It’s fine if it’s located in an area entirely accessible for the lifetime of the structure for when failure and replacement might occur, but otherwise, it’s pain waiting to fail imho.

Alas, the cost of longtermism mindset (“This is the last time someone will need to touch what I’ve built for the next 100 years, at a minimum”).

gambitingNov 26, 2026, 5:05 PM
TIL!
omnimusNov 26, 2026, 6:16 PM
Burning trash can be pretty harmless if done properly. In EU it usually is done propelry because of regulations.
__MatrixMan__Nov 26, 2026, 6:30 PM
I doubt the practice will persist if the future forces us to take carbon capture seriously. Whatever energy you get from burning the trash you're gonna have to spend on whatever scheme pulls the carbon from the air. Leaving it as plastic and burying it cuts out the middleman.
omnimusNov 26, 2026, 6:13 PM
Usually it's for heat only? In some places they burn trash (plastic) for heat generation.
yxhuvudNov 26, 2026, 3:40 PM
Not for distribution, as it needs to be hot enough to kill legionalla.
teifererNov 26, 2026, 4:29 PM
District heating is typically a closed loop high pressure system which is not just pute water but has some nasty additives. You then use a heat exchanger in your basement to heat up your hot water coming out of the tap.

Besides, 45C is what needs to go into the data center. What comes out of it is much hotter and you then need to bring it down to 45C. For example by heating your house or your shower water.

adrianNNov 26, 2026, 6:37 PM
Transfer the heat and upgrade it with a heat pump
fortran77Nov 27, 2026, 1:04 AM
Also right about where Legionella likes it. You'd still need to get it up to 60 before anyone showers in it.
__MatrixMan__Nov 27, 2026, 4:47 PM
Touchet. Solvable with heat exchangers though.
deadbabeNov 26, 2026, 3:37 PM
People do not want to bathe in your unethical cursed water that was used to cool chips creating AI content trained on stolen data!
teifererNov 26, 2026, 4:33 PM
Not sure if sarcastic or not ..

Alternative is to evaporate the water. Not sure how that is more ethical.

As an ethically inclined meat eater (i.e. non-vegetarian) I often prefer eating the parts of the animal that are considered "waste". Sausages (full of things like intestines, liver etc), skewers with chicken hearts, that kind of stuff. Similar to the hot water, at least you can do sth meaningful with the "waste". Arguably more ethical than throwing it away (into which I count biogas generation).

konschubertNov 26, 2026, 4:41 PM
Many parts of the world have abundant rain or sea water, evaporating it should be just fine.
teifererNov 28, 2026, 8:04 AM
I think that does not reflect reality. In large parts of the world, fresh water is already a scarce resource and it is only getting worse. Just ask the average US farmer and how their aquifer is doing. Evaporating that for AI is terrible.

Cooling your data center with sea water is harder than it sounds like.

konschubertNov 28, 2026, 8:34 AM
While you talk to that farmer, ask him how much water his farm uses.

Farms overall use much, much much much more water than data centres.

My point is not whataboutism, my point is that we talk about a tiny thing and ignore the big thing.

A lot of farm output is energy crops to be burned or gassed in a gas tank. At least here in Europe.

And I’m not vegetarian myself but if we’re going to have an argument about water usage, we have to talk about meat consumption.

__MatrixMan__Nov 26, 2026, 6:33 PM
It's called a heat exchanger. Or is the energy itself cursed?
deadbabeNov 26, 2026, 6:51 PM
A thought experiment, imagine a powerplant that was powered entirely by the forced labor of enslaved people who receive no compensation for their work spinning up energy for the powerplant. Would you use that energy? To heat your home, to cook your food, to power your electronics? Bad energy.

With these heat exchangers, its exactly the same.

__MatrixMan__Nov 26, 2026, 7:47 PM
If you're morally outraged by something, you're probably better off actively interfering with its operation. Like... get off your high horse and go free the slaves, violently if necessary.

Coming up with ways of accounting for which quanta of energy is bad and which are good as an elaborate way of having washed your hands of the situation is not going to achieve anything.

deadbabeNov 26, 2026, 9:48 PM
So should vegans kill carnivores?
rixedNov 27, 2026, 4:46 AM
They should certainly try to make the number of meat consumers go down, and they do, by proselytism and education and arguing for non meat options becoming the norm, thus making it easier for non militant vegetarian to lower their own meat consumption (thank you for that btw)
__MatrixMan__Nov 27, 2026, 7:57 AM
That's a little out of proportion, I'd say. But I'd respect a bit of sabotage.

If you're not spending money and not interfering, you're invisible. These are the yes's and no's of communicating with capital.

deadbabeNov 27, 2026, 6:39 PM
So what you’re saying is they should spread prions through meat, rendering them dangerous to eat and killing off the people who eat the meat, leaving only the vegetarians and vegans to dominate.
aziaziaziNov 28, 2026, 1:40 PM
Yes that’s the idea. Same strategy as when we removed the unique income of slave masters, leading them to an inevitable poverty and death. Some of them adapted by imitating the non-segregationists around through.
dachrisNov 26, 2026, 4:04 PM
There was a satire in Germany many years ago where someone sold a filter that would filter out electricity from nuclear power plants.

Business opportunity: sell a device that restores the water's pureness by mining bitcoin into your account.

margalabargalaNov 26, 2026, 4:01 PM
At least one atom that has passed through your body, also passed through Hitler. You're already tainted.
throw0101cNov 26, 2026, 4:44 PM
ASHRAE TC 9.9, "Mission Critical Facilities", members are IT folks, and they have defined a Category/Class "A4" that have dry-bulb operating temperatures in the 5-45˚C range:

* https://www.upsite.com/blog/the-importance-of-mutual-underst...

There's also:

> For those familiar with the liquid cooling guidelines, the most obvious change will be that of the Liquid Cooling class designations. Previously, the classes were designated W1, W2, W3, W4 and W5. Each of those classes had a lower temperature limit of 2°C, while the upper limits were 17°C, 27°C, 32°C, 45°C, and Over 45°C respectively. The deficiency in the original designations didn’t really appear until the debate began over adding a class between 32°C and 45°C.

> […] In the end, due to the need for enhanced flexibility, not to mention making it easier for users to remember what temperature goes with the Class, the 5th Edition redesignated the classes based on their upper temperature limit – therefore the classes are now W17, W27, W32, NEW class W40, W45, and the now named W+.

* https://www.upsite.com/blog/what-you-need-to-know-about-ashr...

So >35C isn't entirely unknown already.

* https://www.ashrae.org/technical-resources/bookstore/datacom...

* https://greencalculus.com/standards/ashrae-tc-9-9-thermal-gu...

GMoromisatoNov 26, 2026, 6:22 PM
This also makes orbital datacenters more economical since radiators can be smaller at higher temperatures.
marginalia_nuNov 26, 2026, 7:36 PM
Shouldn't matter very for this application. In space you're using blackbody radiation to get rid of excess heat, and that only does meaningful work if you use a heat exchanger first to increase the temperature of the medium on the radiator side (basically same principle as a refrigerator) since the Stefan–Boltzmann law says thermal radiation per area is P∝T^4 (and blackbody radiation is itself pretty anemic unless temperatures are pretty high).

Also worth noting that only the projected area matters for blackbody radiation so having a convoluted high surface area low volume radiator like we do when air or liquid cooling basically does bupkis.

postalratNov 26, 2026, 8:24 PM
I feel the way we get space data centers is to create processing blocks as large as the silicon solar cells. With data moving one way across multiple meters as it is processed.
fookerNov 27, 2026, 4:12 AM
The trend is only going to continue, I'll not be surprised if we see chips and electronics that operate in increasingly higher temperatures.

We have plenty of headroom before we reach the melting points of the components, so it's a nice incremental engineering problem to solve.

emil-lpNov 26, 2026, 7:14 PM
More economical than what?
shepherdjerredNov 26, 2026, 7:26 PM
More economical than previous orbital data center concepts
yreadNov 26, 2026, 3:05 PM
Datacenters here on Earth will be much less of a problem with less water consumption because they won't need evaporative cooling
mschuster91Nov 26, 2026, 3:34 PM
Evaporative cooling seems to be some American nonsense.

Here in Europe, the only things using evaporative cooling are large power plants and industrial processes needing to shed a lot of heat. Everything else is either using pure air cooling, cooling based on a nearby river, or in extremely modern/research projects, dump their excess heat into district heating systems [1][2].

For me as a German, reading about Americans complain about water usage for datacenters was a real culture shock.

[1] https://www.br.de/nachrichten/bayern/noch-haeufig-ungenutzte...

[2] https://www.bayern-innovativ.de/emagazin/detail/tu-muenchen-...

maelnNov 26, 2026, 3:53 PM
> Evaporative cooling seems to be some American nonsense.

Don't quote me on that, but I remember OVH proudly advertising their new "passive" DC cooling system, which was based on evaporative cooling. The idea of using less energy, but more water was sold as "green" a few years back.

A lot of the new DC getting out of the ground in China where also designed with evaporative cooling in mind. It's definitely not an "american nonsense". What is non sensed though is that both China and the U.S are building a lot of their DC designed with evaporative cooling in water stressed region right now. While it makes sense in terms of cooling (drier air makes evaporative cooling better), I don't think I have to mention the obvious problem of pumping tons of water in dry region.

hommelixNov 26, 2026, 6:05 PM
How I remember the passive cooling of OVH, it was only air. The building ventilation shaft was made with larger opening for fresh air at the bottom and a smaller section chimney at the top. The draft due to the hot air speeding at the chimney pulls the cold air at the bottom.

Unfortunately at the Strasbourg DC, there was no flaps to close the air inlet during fire and this lead to the event that turned a few servers into ash.

adrianNNov 26, 2026, 6:42 PM
Whether water usage is a problem or not entirely depends on the local climate.
entropeNov 26, 2026, 3:49 PM
Some European data centers use evaporative cooling because they got permits long ago, they don't have the physical space for a non-evaporative system, or both. [1] and [2] (both Dutch, because I happened to go there for spring break this year and saw the coverage then) are two examples.

[1]- https://www.techzine.nl/nieuws/infrastructure/577227/datacen... [2]- https://www.nrc.nl/nieuws/2026/08/16/nieuw-amerikaans-datace...

citrin_ruNov 26, 2026, 5:16 PM
> Evaporative cooling seems to be some American nonsense

Evaporative cooling saves energy (compare to A/C like systems with a compressor) so if water is abundant (in some climates it is) it makes sense.

m4rtinkNov 26, 2026, 3:44 PM
It's not just modern stuff - steel works and other heavy industry used process powered district heating for a very long time. In some cases it created problems when the enterprise went bankrupt or fragmented and suddenly the process that is providing the district heating might no longer be running. :P
coryrcNov 26, 2026, 7:38 PM
In much of America, you can cheaply stop other people developing their own property by claiming it affects the environment. Here in Seattle, the local labor unions are blocking a grocery store from opening, in a building which used to be a grocery store, by claiming the environmental impact of parking has not been sufficiently measured: https://www.seattletimes.com/business/retail/who-doesnt-want...

So if anyone anywhere just doesn't want data centers, they'll throw every claim and go with whatever sticks.

Oddly, the few immediate claims, like impact from sound levels, they won't support actually writing laws preventing it, because it only affects dozens of people and the rest can't be bothered because it might reduce their leverage in stopping the project, so the immediate neighbors end up getting screwed when projects do get approved...

PeterHolzwarthNov 27, 2026, 1:10 AM
I don't see any evidence the unions are behind that lobby group - even your linked article fails to demonstrate anything other than speculation.
InsidiousWombatNov 26, 2026, 4:33 PM
Its effect of density. Average datacenter takes far less power than one filled to brim with GPUs. They just don't want to spend extra on area for coolers
howard941Nov 26, 2026, 5:19 PM
America has a long history of using in-room swamp coolers to endure summer. They don't work well in humid climates of course.
nekusarNov 26, 2026, 3:33 PM
[flagged]
maelnNov 26, 2026, 3:49 PM
> When water evaporates, where does it go?

> 1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)

> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain

Problem is, as far as I know, DC do not use rain / river / aquifer water straight up. Water needs to be processed, and processing water is not free. So you use a significant amount of energy to process water who will be just dumped to release heat.

The other thing is, where the water is coming from and where it goes is very important. A lot of DC in China and the U.S right now are being built in drought prone regions. When you evaporate the water, there is no guarantee that it will rain in the same region. So you are draining the aquifer of already water-stressed region, to have it dumped as rain somewhere else that might not have water stress.

coredog64Nov 26, 2026, 4:48 PM
The Palo Verde Nuclear Generating Station uses residential gray water as it's feed source for evaporative cooling. If toilet water can manage several gigawatts of nuclear generation, it'll be fine for cooling racks of Blackwell GPUs.
PeterHolzwarthNov 27, 2026, 1:11 AM
Gray water is not toilet water.
mschuster91Nov 27, 2026, 12:39 PM
You need to retrofit every home around datacenters and build separate sewer lines for this grey water - which is why PV NPP uses treated sewage water, aka the effluent of wastewater treatment plants [1], instead.

[1] https://cronkitenews.azpbs.org/2020/02/25/palo-verde-nuclear...

eminence32Nov 26, 2026, 3:41 PM
Obviously the water isn't destroyed, but the problem is when you pull water out of some deep aquifer. It make take a Very Long Time before that rain can refill the aquifer. Assuming it falls in the right place and not 1000 miles away.

Globally over very long time horizons datacenter water usage is neutral. But over the shorter time periods that we care about, it moves the water around in problematic ways.

adrian_bNov 26, 2026, 3:44 PM
Frequently, the water that goes into clouds from some place will not return through rain in the same place.

If you evaporate water in a place where it seldom rains, it is likely that you will make that place drier than it already is, so you should avoid this.

Only for datacenters built in rainy places it does not matter whether they evaporate water.

coredog64Nov 26, 2026, 4:52 PM
So like Oregon along a river, Loudoun County in Virginia, or central Ohio? One might almost think that the datacenter operators take this into account.

https://www.ncei.noaa.gov/access/monitoring/climate-at-a-gla...

https://www.currentresults.com/Weather/Ohio/average-yearly-p...

mschuster91Nov 26, 2026, 3:37 PM
> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain

The problem is, you can do this on say, a large lake. No big deal there, as long as you can manage fouling. Or you can do this on an ocean if you desalinate the water. There, your assumption holds.

But if your water supply is a small river that already has trouble supplying downstream with enough (clean) water? Suddenly the "lost" water is a real issue for the downstream communities depending on it, either because they have to compensate by digging wells into groundwater aquifers that often have replenishment times measured in years if not decades or centuries, or because they have to deal with riverbeds running dry in the worst case, which places them in an even worse bind given they have to discharge the water from sewage treatment plants in a river that can dilute it enough with fresh water.

Friends don't let friends run evaporative cooling if there is literally any other way.

nekusarNov 26, 2026, 3:43 PM
You make a good point. The current USA push for datacenters is more a game of how much they can externalize the costs to everyone else, and internalize all the gains.

Geothermal is great at heat/cooling control. So is electric condensation of atmospheric water. It's a big energy gathering and controlling problem. And more money can reduce or near eliminate the negatives.

The USA companies are not forced to pay appropriately for current great teach for electricity and cooling. They instead force communities to "deal with it".

And no, data centers do not need drinkable water for the compute. We could have had water cleaning, recycling units, etc. Nope, "too expensive".

swiftcoderNov 26, 2026, 4:15 PM
> And no, data centers do not need drinkable water for the compute

A bunch of datacentres run on water that is significantly purer than plain old drinking water - they sometimes need a pre-treatment step to purify the incoming utility water. Apparently all those tasty dissolved solids can wreak havoc in a cooling loop...

K0baltNov 26, 2026, 10:40 PM
Maybe this is a plan to make their products more desirable while cutting the service life so they don’t last well for secondary markets . Afaik no way to run hotter without shortening service life.
WaterluvianNov 26, 2026, 5:14 PM
Are there any Factorio-like games that treat heat gradients as a kind of spatial resource? Like in some sci fi factory you’ve got an iron smelter pressed right up against your data refinery?
CivilRNov 26, 2026, 5:20 PM
Oxygen Not Included has a lot of heat management but it's more of a colony sim.
tjbrockNov 26, 2026, 5:52 PM
Second this. One of my favorite games and it has such crazy complexity with heat management and everything else
shepherdjerredNov 26, 2026, 7:27 PM
Factorio has this mechanic in the endgame of its Space Age expansion

https://wiki.factorio.com/Aquilo#:~:text=to%20pave%20ice.-,F...

There's also a similar mechanic for nuclear reactors

elliefurnaceNov 28, 2026, 2:07 AM
[dead]
leni536Nov 26, 2026, 5:47 PM
I assume this also means more water moved for the same power and target die temperature. I wonder what other engineering considerations follow from that.
dextrousNov 26, 2026, 5:47 PM
Excellent Buggles lyric reference as the lead-in, thank you! I always post another line in these cases

“I met your children. What did you tell them?”

exabrialNov 27, 2026, 3:06 AM
45c is about 113 freedom for this so inclined
jeffwassNov 26, 2026, 4:37 PM
What fraction of a typical data center’s power usage comes from the chillers?
KaiserProNov 26, 2026, 4:40 PM
Depends on the datacentre.

for "traditional" datacenters, its up to half. Ie you put in one megawatt and then spend a megawatt to move that heat outside. (although its never quite that bad, you need to spec it for the hottest day in that area + 10%)

If you use evaporative cooling, then you cut your cooling bill significantly (ie top up chillers plus cooling loop pumps)

latchkeyNov 26, 2026, 5:11 PM
moringNov 27, 2026, 9:12 AM
> We're approaching a point where industry advances are answering many of the objections (the real ones, not the hysterical ones) raised by the anti-data center movement.

> Much lower energy use, water consumption down by 85 percent to 90 percent, higher efficiency and lower costs. Not a bad deal, right?

No, we're approaching a point where the author of this article learns about the Jevons Paradox.

tomaskafkaNov 26, 2026, 8:00 PM
Excellent, hyperscalers don’t need to care about climate anymore as ability to work in 45 degrees Celsius means AI will comfortably keep working through human extinction level temperatures just fine.

Shareholders in climatized New Zealand bunkers rejoice.

imp0catNov 26, 2026, 8:21 PM
Also various forms of fungi. Fun times ahead! https://time.com/article/2026/10/27/why-dangerous-fungi-are-...
tomaskafkaNov 27, 2026, 12:15 PM
Yes. Just yesterday I encountered a thread with people sharing effect of anti-fungal treatments, it was quite horrific to read as fungi are so similar to us, that you basically need to semi-poison yourself to kill them, similar to chemotheraphy.
jfkimmesNov 26, 2026, 4:36 PM
Wow, this contains so many AI-isms that it is legitimately hard to read for me. Shocking to see such blatant slop in a journalistic publication (vs. a random blog post).

https://www.pangram.com/history/6901a6ab-fc82-40bc-9be6-f67a...

cadamsdotcomNov 27, 2026, 1:06 AM
Why not build a day spa next to every datacenter!

A whole grid of hot tubs and saunas, as far as the eye can see, heated, all for free..

Good for the approval ratings AND your body.

originiNov 26, 2026, 4:53 PM
I don't get it anyway.

These DC are big and create a lot of heat. Why is there nothing around them which would take that heat off them?

Can't we even use a heatpump to even take it to make a higher difference for some industries etc.?

Suckerburg even destroyed a CPU based DC to build it up again as a GPU based on. They can build stuff

cucumber3732842Nov 26, 2026, 2:59 PM
Sooooo... downsize everything, still run chillers and have better capex for the same-ish opex?

There's no inherent reason this has to be a hard cut or that a hard cut to a different cooling architecture will be the right way to go.

samuelknightNov 26, 2026, 3:25 PM
No. Similar capex and better opex. Chillers are not very expensive compared to the chips. Data center economics is built around PUE, a ratio of total power / IT power. The optimal data center has PUE=1, a real data center is >1 because some power has to go to facilities and cooling.
InsidiousWombatNov 26, 2026, 4:34 PM
Google's fleet wide PUE is around 1.1
lokarNov 26, 2026, 3:08 PM
Sure, it expands to space of workable trade offs. Some times that will mean no chillers.
dist-epochNov 26, 2026, 6:18 PM
Sahara land suddenly becoming very valuable.
mvcNov 26, 2026, 7:26 PM
Glad the computers will continue to be operable when their rampant use makes planet hotter. Are us humans going to get a similar upgrade?
FLeXMurphyNov 26, 2026, 4:13 PM
We haven't noticed it because we've literally been doing this for decades in non-data-center applications. Holy marketing batmans.
hinkleyNov 26, 2026, 5:32 PM
[dead]
LoganDarkNov 26, 2026, 5:21 PM
[dead]
arjendevosNov 26, 2026, 6:44 PM
[dead]
ZiiSNov 26, 2026, 3:51 PM
I know it is irrational but factual documentaries like the matrix do make me think if we should optimize machines to need body temperature fluids.